PLC Simulator
VFD / VSD commissioning simulator

Variable frequency drive training from terminals to trip history.

A vendor-neutral, browser-based VFD simulator for technicians and controls engineers. Wire it. Parameterise it. Prove STO. Run a real process load. Diagnose the fault from evidence.

No install · works on desktop, tablet and phone · training model, not a manufacturer configurator

Quick answer: a VFD simulator should let you commission the complete drive system—not only change frequency. This one connects terminal wiring, motor data, command and reference sources, STO, process load, live measurements, faults and a commissioning record in one browser workbench.

Live drive telemetryRUNNING · 38.0 Hz
Industrial variable frequency drive with keypad, line, motor, control and STO terminals
Output38.0 Hz
Motor1102 rpm
Current6.7 A
DC bus565 V
Load68%
Pro commissioning path4 scenarios · saved progress · PLC/HMI handoff

The guide is public. The working lab is Pro.

Use this page to understand the equipment, workflow and terminology. Sign in to the Pro path to operate the full physics model, complete commissioning evidence, inject faults and continue into a prepared PLC–HMI Sandbox project.

  1. 01

    Local keypad & motor ID

    First start

  2. 02

    Conveyor commissioning

    Foundation

  3. 03

    Pump with 4–20 mA reference

    Process control

  4. 04

    Fieldbus fan control

    Networked drive

  5. 05

    Drive diagnosis bay

    Advanced

Drive system visual guide

From three-phase supply to verified conveyor speed

A VFD only makes sense as part of a system. Follow the energy path, control wiring, motor data, load response and diagnostic evidence before opening the interactive commissioning workbench.

Variable frequency drive control panel with three-phase protection, contactor, PLC control wiring and induction motor
01Separate the power path, control path and motor circuit before treating the drive as one black box.
VFD internal power conversion from three-phase AC through rectifier and DC bus to PWM motor output
02See how the rectifier, DC bus and inverter convert fixed-frequency supply into controlled three-phase motor output.
Technician entering motor nameplate values and ramp parameters while commissioning a conveyor VFD
03Enter the connected motor’s data, operating limits, ramps and command sources before the loaded proving run.
PLC to VFD wiring for run, direction, analog speed reference, drive feedback, safety stop and motor earth
04Connect discrete commands, analog reference, feedback, safety and protective earth as separate testable circuits.
Technician diagnosing a tripped conveyor VFD using current measurement, drive status and mechanical load evidence
05Use current, speed, drive history and the physical load to distinguish an electrical trip from a jammed machine.
PLC-controlled VFD conveyor with commanded speed, actual motor speed, current and acceleration trend
06Verify the outcome: the actual motor follows the command through acceleration, running load and controlled stop.

Content depth

The complete commissioning loop—not a speed slider.

The workbench connects electrical installation, motor data, application behaviour, safety proving and fault diagnosis. That is the sequence technicians face at a real drive cabinet.

Terminal-level wiring

Line, PE, motor phases, dual-channel STO, hardwired run and analog reference—not a single fake “connected” toggle.

Parameter commissioning

Motor nameplate, stationary motor identification, min/max limits, ramps, command source and speed-reference source against a real job sheet.

Dynamic machine loads

Conveyor, centrifugal pump, fan and dynamometer views respond to frequency, load, current and trips.

Drive function trainer

Compare command circuits, reference functions, stop modes, flying start, PID, current limiting and motor-control modes.

Synchronized 2D and 3D

Keep terminals and codes precise in 2D, then inspect the same live motor, shaft and process response in an orbitable 3D lab.

Evidence-led diagnosis

Live current, DC bus, temperature, speed error and five-entry trip history separate electrical and mechanical causes.

Safety workflow

Safe isolation before wiring, both STO channels, uncoupled bump test, direction confirmation and loaded proving run.

Six fault families

Jammed load, phase loss, supply collapse, blocked cooling, open STO and aggressive deceleration behaviour.

Shipped features · verified 9 August 2026

VFD/VSD capabilities available now.

These are live product capabilities, not roadmap promises. 5 guided VFD/VSD commissioning jobs now share one instrumented runtime across technical 2D and interactive 3D views; the separate function explorer adds 12 standalone experiments.

View the full capability matrix
Live

Installation

Three-phase line, PE, U/V/W motor, digital, analog and dual-channel STO terminal work

Live

Commissioning

Motor nameplate, stationary motor ID, operating limits, ramps, command source and speed-reference source

Live

Control

2-wire and 3-wire commands; keypad, terminal and fieldbus sources; jog, forward/reverse and control/status words

Live

Functions

Analog, preset, motor-pot and PID references; skip band, current limit, V/Hz and sensorless-vector control

Live

Stops & restart

Ramp, coast, quick-stop and DC-brake behavior plus flying start and communication-loss response

Live

Applications

Conveyor, centrifugal pump, fan and dynamometer machine-load models

Live

Measurements

Frequency, rpm, current, torque, DC-bus voltage, temperature and load

Live

Diagnostics

Seven fault conditions, five-entry trip history and cause-aware reset permissives

Live

Guidance

Step-by-step actions, reasons, expected evidence and progressive hints for every job

Live

Evidence

Isolation, STO, direction, unloaded and loaded proving checks in a commissioning record

Live

Platform

No-install responsive browser UI, descriptive technical images and reduced-motion support

Function and code library

Learn what each function changes—then prove it on the same motor.

These are authored guides for the drive behaviors people actually search and troubleshoot. Each uses a stable vendor-neutral training code, explains the physical consequence, names the evidence to watch and deep-links to the matching function lab. Exact manufacturer parameter numbers still come from the installed drive manual.

Showing 12 of 12 authored guides.

F-20

VFD 2-Wire vs 3-Wire Control

A 2-wire VFD command follows a maintained contact: closed means run and open means stop. A 3-wire circuit uses momentary start and stop inputs; the drive latches the run request after the start pulse is released.

Explain and test →
F-25

VFD Flying Start Explained

Flying start—also called speed search or catch on the fly—estimates the speed and direction of an already rotating motor before the drive reapplies controlled torque.

Explain and test →
D-01

VFD Fault Codes and Diagnostic Method

A VFD fault code identifies which protection function operated; it does not by itself prove the failed component. Diagnose with the code, first-changing measurement, trip history and machine condition together.

Explain and test →
F-20

VFD Run Command Sources

A VFD run command can come from the local keypad, hardwired terminals or a fieldbus control word. The selected source must match the signal the PLC or operator is actually sending.

Explain and test →
F-31

VFD Jog Mode and Jog Frequency

Jog is a deliberate low-speed command that temporarily overrides the normal speed reference while the jog input or keypad command is active.

Explain and test →
F-23

VFD Speed Reference Sources

The speed reference is the requested output frequency or process demand. It can come from the keypad, 0–10 V, 4–20 mA, preset speeds, a motorized potentiometer, PID output or a fieldbus word.

Explain and test →
F-22

VFD Stop Modes: Ramp, Coast, Quick Stop and DC Brake

A VFD can ramp the frequency down, remove torque and coast, use a faster quick-stop ramp, or apply DC injection braking. Each produces a different current, torque, stopping time and DC-bus response.

Explain and test →
F-61–F-63

VFD Preset Speeds

Preset speeds are stored frequency references selected by digital inputs or control bits. They provide repeatable operating points without an analog signal.

Explain and test →
F-71–F-72

VFD PID Control for Pumps and Fans

A drive PID function compares a process setpoint with transmitter feedback and continuously changes motor frequency to reduce the error.

Explain and test →
F-41

VFD Current Limit and Stall Protection

Current limiting caps drive output current and therefore available motor torque. The drive may slow or extend acceleration instead of immediately tripping when the load demand reaches that limit.

Explain and test →
F-21

V/Hz vs Sensorless Vector VFD Control

V/Hz control applies a frequency-to-voltage profile and is simple and robust. Sensorless vector control uses a motor model to regulate flux and torque more accurately, especially at low speed and changing load.

Explain and test →
S-01

VFD Safe Torque Off (STO)

Safe torque off prevents the drive from generating motor torque when its safety channels are de-energized. It does not isolate mains power and does not necessarily stop a moving machine quickly.

Explain and test →

Visual field guide

Eight diagrams that connect the screen to the real job.

Each visual answers a commissioning question the interactive bench then lets you test. They use vendor-neutral terminal names and component relationships so the lesson transfers without pretending every drive has identical parameter numbers.

Annotated VFD terminal map showing L1 L2 L3 supply, U V W motor output, digital run input, analog speed reference and two STO channels

Installation

Read the drive as five separate circuits

Power, motor, control, analog and safety connections have different purposes and failure symptoms. The lab keeps their terminals visible instead of reducing commissioning to one connected switch.

Seven-step VFD commissioning workflow from safe isolation and wiring to nameplate entry, STO proving, direction test, loaded run and handover

Workflow

Follow the job in a defensible order

Isolation comes before terminal work; motor identification comes before running; an uncoupled direction check comes before the loaded proving run. Each completed check becomes evidence in the record.

Induction motor nameplate values for voltage, frequency, power, current and speed mapped into VFD motor-data parameters

Parameters

Translate the nameplate without guessing

Rated voltage, frequency, current, speed and power describe the motor the drive must control and protect. Wrong data can produce poor torque, misleading load values or nuisance trips.

Dual-channel VFD safe torque off diagram with emergency stop, safety relay, STO A and STO B paths and torque-disabled drive display

Functional safety

Prove both STO channels

The safety relay feeds two independent drive inputs. The motor can be stopped by command while torque remains available; STO is the separate safety function that prevents torque generation.

PLC analog output wired as a 4 to 20 milliamp VFD speed reference, showing 12.8 milliamps scaled to 55 percent and 27.5 hertz

Control I/O

Commission the entire analog reference

The signal must be wired to AI1 and analog common, configured for current rather than voltage, and scaled to the intended frequency range. A live loop value separates wiring faults from scaling faults.

VFD application load models for a conveyor, centrifugal pump, ventilation fan and dynamometer test bench

Machine physics

See why the application changes the drive

A loaded conveyor behaves differently from a centrifugal pump or fan. The process model changes current, torque, speed response and likely trip conditions rather than animating every motor identically.

VFD diagnostic trend of speed, current, DC bus voltage and drive temperature during a mechanical load step

Diagnostics

Diagnose from measurements, not the trip name alone

Frequency, actual speed, current, DC bus and temperature create a fault signature. A load step with stable supply evidence points somewhere different from a falling DC bus or rising heat-sink temperature.

VFD fault history showing overcurrent, undervoltage and overtemperature trips with measured evidence and reset permissives

Recovery

Remove the cause before resetting

Trip history preserves evidence after the machine stops. Reset remains blocked while the injected cause or run request is active, reinforcing recovery as a controlled commissioning step rather than a reflex.

Practical method

How to commission a VFD in the simulator.

The sequence is deliberately conservative. It separates installation, configuration, functional proving and diagnosis so a symptom is not masked by changing several things at once.

For real equipment, the drive manual, approved schematic, motor data, machine risk assessment and site isolation procedure always take precedence.

  1. 01

    Isolate and inspect

    Open the upstream isolator, prove the training circuit dead and inspect line, motor, earth, control and safety conductors before changing a connection.

  2. 02

    Wire the power path

    Connect L1/L2/L3 and protective earth to the drive, then U/V/W and the motor protective conductor. Keep supply and motor terminals conceptually separate.

  3. 03

    Wire command and safety

    Land the digital run command and common, the analog or fieldbus reference path, and both STO channels required by the job.

  4. 04

    Enter motor data

    Copy rated volts, hertz, current, speed and power from the nameplate. Set the application limits and ramps from the commissioning sheet.

  5. 05

    Prove locally first

    Use keypad control for an uncoupled bump test. Confirm rotation, actual speed, current and stop response before transferring control to the PLC.

  6. 06

    Transfer control source

    Select terminal or fieldbus command and the required reference source. Prove minimum, midpoint and maximum demand rather than checking only one value.

  7. 07

    Run the real load model

    Couple the conveyor, pump, fan or dynamometer. Compare current, torque, speed error, DC bus and temperature with the unloaded baseline.

  8. 08

    Test faults and document

    Diagnose the injected trip from evidence, remove the cause, satisfy reset permissives and complete the commissioning record.

Parameter guide

The parameter groups that make or break a start-up.

Manufacturers use different numbers and menu structures, but the engineering questions remain recognizable. The simulator groups them by purpose so learners understand what they are setting before memorising a vendor menu.

Parameter groupTypical entriesCommissioning reason
Motor identityRated volts, hertz, amps, rpm and powerProtection, slip and load calculations start with correct motor data.
Operating limitsMinimum, maximum and base frequencyLimits must suit the motor, machine and required process range.
RampsAcceleration and deceleration timeAggressive acceleration raises current; aggressive deceleration can raise the DC bus.
Command sourceKeypad, terminals or fieldbusA healthy drive will not run if it is listening to a different command source.
Reference sourceKeypad setpoint, AI1 or fieldbus wordThe run command and speed reference can come from different places.
ProtectionCurrent limit, overload and reset behaviourProtection should match the motor and application, not hide a mechanical problem.

Too-short acceleration

Demanding torque faster than the motor and drive can deliver raises current and can produce overcurrent or current-limit operation.

Too-short deceleration

A high-inertia load can regenerate energy into the DC bus. The simulation exposes the resulting voltage rise and trip evidence.

Wrong motor current

Protection and load indication become unreliable when the drive is configured for a different motor than the one connected.

Local, terminals or PLC

Command source and speed reference are separate decisions.

A drive can receive its run command from a terminal while receiving speed over an analog input, or receive both over a network. When the source selection is wrong, the drive may show ready with no response—an easy condition to misdiagnose as failed hardware.

Keypad / local

Best used for
Initial uncoupled proving and service checks
Prove during commissioning
Local indication, direction, minimum speed and stop response.

Hardwired terminals

Best used for
Simple machines and discrete PLC control
Prove during commissioning
DI common, run input logic, direction and loss-of-command behaviour.

4–20 mA reference

Best used for
Process speed demand from PLC or controller
Prove during commissioning
Loop current, live input value, signal type and min/max scaling.

Fieldbus

Best used for
Integrated PLC diagnostics and control
Prove during commissioning
Control word, reference word, status word and communication-loss response.

Symptom-led diagnostic

VFD will not run: follow command to torque in six checks.

Do not start by changing random parameters. Split the system at observable boundaries—ready state, safety permit, run command, speed reference, drive output and mechanical response—so every reading either proves a stage or narrows the fault.

  1. 01

    Is the drive actually ready?

    Read the status and active fault before changing a parameter. Confirm control power, a healthy DC bus, no active trip and no start inhibit. A blank display, faulted drive and ready drive are three different diagnoses.

    Record: Display state, active fault, DC-bus value and ready bit

  2. 02

    Are STO and external permits healthy?

    Prove both STO channels and any external enable or safety-relay feedback. An ordinary STOP command and safe torque off are not interchangeable: STO can leave the drive powered and communicating while torque remains disabled.

    Record: STO A/B status, enable input and safety-chain indication

  3. 03

    Is the drive listening to the command you are sending?

    Compare the selected command source with the live keypad, terminal or fieldbus command. A terminal can switch correctly while the drive is still configured for keypad control; a PLC bit can be true while the control word is not owned or enabled.

    Record: Selected command source and live run-command state

  4. 04

    Is there a usable speed reference?

    A valid run command with a zero, incorrectly scaled or wrong-source reference can produce a ready drive and stationary motor. Check the selected reference source, live value, engineering units, minimum frequency and direction.

    Record: Selected reference, raw input and commanded hertz

  5. 05

    Does the drive produce output?

    If commanded frequency stays at zero, remain in command, reference and inhibit logic. If frequency rises but current and motor speed do not, inspect output wiring, isolation, motor connection and feedback. If current rises without speed, investigate the mechanical load or brake.

    Record: Output hertz, motor current, actual speed and torque/load

  6. 06

    Can it stop, fault and recover correctly?

    Remove the active cause before resetting, clear the run request where required, then prove a controlled restart. Save the before-and-after evidence so a reset does not erase the only useful fault signature.

    Record: Trip history, removed cause, reset permissive and proving run

Practise the two most-missed boundaries.

The free micro-lab makes you prove both the run permission and a non-zero speed reference before the motor moves.

Diagnose a VFD start free

Troubleshooting logic

Read the fault as a system response.

An overcurrent trip does not automatically mean a defective drive. A jammed conveyor, an unrealistically short acceleration ramp or incorrect motor data can create similar symptoms. Undervoltage begins with supply and DC-bus evidence; overtemperature begins with load, cooling and temperature history; STO status begins with the safety channels, not the ordinary run command.

The fault bay therefore exposes measurements and preserves history. The learner identifies which evidence changed first, removes the active cause, stops the command and only then resets. That sequence is transferable to manufacturer-specific diagnostics.

One model, two views

Technical 2D for precision. Interactive 3D for spatial and mechanical understanding.

The 2D view keeps terminal marks, parameter codes, keypad values and meter readings fixed and legible on desktop and mobile. It remains the primary engineering interface for wiring and evidence.

The optional 3D lab makes the cabinet, cable route, induction motor, shaft, coupling and driven equipment spatially clear. It is not a disconnected animation: both views consume the same frequency, signed rpm, current, direction, load and trip state, with a reduced-motion fallback and automatic return to 2D if WebGL is unavailable.

Continue the signal path

Connect drive commissioning to PLC and field wiring.

Use the commissioning checklist for the complete evidence sequence, the wiring tutor for physical terminations, motor-control circuits for contactors and interlocks, and the protocol guides for command/status mapping.

Questions

Frequently asked.

You can wire line, motor, earth, run, analog-reference and STO terminals; enter motor nameplate data; perform stationary motor identification; select keypad, terminal or fieldbus control; run conveyor, pump and fan loads; observe live frequency, speed, current, torque, DC-bus voltage and temperature; and diagnose phase loss, undervoltage, overtemperature, overload, stall and regenerative overvoltage trips.
Real VFD simulator footage

See this exact skill in the working simulator.

Watch the real browser product respond to the task on this page, then try the same practical workflow yourself. No slides, concept mockups, install, or credit card.

Try this in the browser
VFD Simulator — Command, Reference, Feedback and Motor Response

Motor, wiring and VFD path

Connect the control command to physical motor behavior

Move from safe control wiring and contactors into VFD parameters, measurements, faults and PLC command paths.