What you will be able to do
- You can turn a symptom into a path through the circuit and half-split it with one measurement at a time.
- You can say what a PLC input LED, an output LED and a voltage reading each prove, and which one to question next.
- You can repair a broken PLC program from a precise behavioural spec: a held motor, a stop that works, a timer that finishes, a counter that resets.
- You can find an open wire, a reversed sensor or a blown protective device with a simulated multimeter and submit a diagnosis the server checks.
- You can explain why a tripped overload or a blown fuse is a clue to the cause rather than the answer.
- 01
The half-split troubleshooting method
Free15 min · lessonTurn a symptom into a path, take one reading at the half-way point and halve what is left, worked through on a motor that will not start.
- 02
Fix 01: Motor won’t hold
Free4 min · scenarioA start button runs the motor only while it is pressed. Repair the program so the motor remembers it was started.
- 03
Fix 02: STOP is ignored
Free5 min · scenarioThe motor holds itself on but nothing in the program reads STOP. Make STOP break the hold and let a fresh START run it again.
- 04
Fault 1: Photoeye polarity reversal
Free8 min · labA dark photoeye on a pre-wired panel. Measure the supply at the sensor, spot the crossed leads and submit your diagnosis.
- 05
Fault 4: Broken +24 V supply wire to the PLC
Free6 min · labThe power supply is lit and the PLC is dark. Walk the rail from the source until the voltage disappears.
- 06
Reading the symptoms: LEDs, tags and meter readings
Free15 min · lessonAn input LED, an output LED and a voltage reading each prove something different. Read sets of readings and pick the fault location.
- 07
Fix 03: Timer never times out
Free8 min · scenarioA two-second warning delay never finishes because the timer is fed by a momentary button. Keep the countdown alive and let STOP cancel it.
- 08
Fix 04: Counter won’t reset
Pro8 min · scenarioA packing station counts three boxes but the reset button does nothing. Clear the count so the next batch starts from zero.
- 09
Fix 05: Two rungs, one output
Pro8 min · scenarioA cooling fan obeys only one of its two requests because two rungs write the same output. Let one place decide the fan.
- 10
Fix 06: Latch won’t release
Pro10 min · scenarioAn oven trip is remembered but can never be released. Make the reset wait for the cause to be gone and refuse it while the oven is hot.
- 11
Fault 2: Relay contact card swap
Pro8 min · labA safety-OK indicator that never comes on, with the relay coil de-energised as it should be. Find the swapped contact.
- 12
Fault 3: Rail short at the terminal block
Pro7 min · labThe contactor never pulls in and the load side is dark. Probe around the terminal block to find the bridged rail.
- 13
Fault 5: Broken 0 V return wire on the contactor coil
Pro7 min · labThe PLC commands the contactor and nothing engages. Prove both sides of the coil to find the open return.
- 14
Fault 6: Broken signal wire between photoeye and PLC
Pro8 min · labThe sensor LED is on and the PLC input never reacts. Compare the two ends of the signal wire.
- 15
Fault 7: NPN photoeye polarity reversal
Pro6 min · labAn input stuck high with an empty conveyor. Decide whether the sensor leads are crossed or the sensor type is wrong.
- 16
Fault 8: Relay contact card swap, alarm stuck on
Pro10 min · labAn alarm beacon on since power-up with a healthy safety chain. Trace the relay contacts that were fitted the wrong way round.
- 17
Fault 9: Blown 24 V control fuse
Pro10 min · labThe supply indicators are healthy and the 24 V rail is dead. Prove voltage on both sides of the fuse.
- 18
Fault 10: High-resistance solenoid terminal
Pro12 min · labA valve that chatters and measures low only while energised. Use a voltage-drop test under load.
- 19
Fault 11: Thermal overload trip
Pro12 min · labThe control supply is healthy and the contactor cannot energise. Trace the series chain to the open protective contact.
- 20
Fault 12: Welded safety output contact
Pro14 min · labA light curtain is interrupted yet the contactor path stays continuous. Prove whether the relay output actually opens.
- 21
Fault 13: Pt100 open compensation lead
Pro12 min · labAn over-range temperature channel with a sensor-break diagnostic. Compare continuity on the three RTD conductors.
- 22
Fault 14: Reversed thermocouple polarity
Pro10 min · labA temperature that falls as the process heats up. Verify polarity at the input card against the sensor type.
- 23
Fault 15: Analog valve feedback drift
Pro15 min · labA valve display at 50 percent and a PLC reading consistently high. Separate wiring loss from a calibration offset.
- 24
Fault 16: RS-485 terminator disconnected
Pro12 min · labModbus that works slowly and fails at speed on long runs. Check end-to-end termination on the de-energised bus.
- 25
Fault 17: VFD STO channel 1 open
Pro14 min · labThe guard is closed and the drive stays inhibited. Compare both safety output channels at the relay and at the drive.
- 26
Fault 18: Intermittent IO-Link C/Q conductor
Pro14 min · labA powered sensor that drops out when the machine vibrates. Find the conductor that only fails under movement.
- 27
Fault 19: Load cell signal pair reversed
Pro14 min · labA weighing channel that reads backwards under load. Verify the millivolt signal pair against the transmitter.
25 of the units are graded or interactive practice on simulated equipment rather than reading:
- Fix 01: Motor won’t hold: A start button runs the motor only while it is pressed. Repair the program so the motor remembers it was started.
- Fix 02: STOP is ignored: The motor holds itself on but nothing in the program reads STOP. Make STOP break the hold and let a fresh START run it again.
- Fault 1: Photoeye polarity reversal: A dark photoeye on a pre-wired panel. Measure the supply at the sensor, spot the crossed leads and submit your diagnosis.
- Fault 4: Broken +24 V supply wire to the PLC: The power supply is lit and the PLC is dark. Walk the rail from the source until the voltage disappears.
- Fix 03: Timer never times out: A two-second warning delay never finishes because the timer is fed by a momentary button. Keep the countdown alive and let STOP cancel it.
- Fix 04: Counter won’t reset: A packing station counts three boxes but the reset button does nothing. Clear the count so the next batch starts from zero.
- Fix 05: Two rungs, one output: A cooling fan obeys only one of its two requests because two rungs write the same output. Let one place decide the fan.
- Fix 06: Latch won’t release: An oven trip is remembered but can never be released. Make the reset wait for the cause to be gone and refuse it while the oven is hot.
- Fault 2: Relay contact card swap: A safety-OK indicator that never comes on, with the relay coil de-energised as it should be. Find the swapped contact.
- Fault 3: Rail short at the terminal block: The contactor never pulls in and the load side is dark. Probe around the terminal block to find the bridged rail.
- Fault 5: Broken 0 V return wire on the contactor coil: The PLC commands the contactor and nothing engages. Prove both sides of the coil to find the open return.
- Fault 6: Broken signal wire between photoeye and PLC: The sensor LED is on and the PLC input never reacts. Compare the two ends of the signal wire.
- Fault 7: NPN photoeye polarity reversal: An input stuck high with an empty conveyor. Decide whether the sensor leads are crossed or the sensor type is wrong.
- Fault 8: Relay contact card swap, alarm stuck on: An alarm beacon on since power-up with a healthy safety chain. Trace the relay contacts that were fitted the wrong way round.
- Fault 9: Blown 24 V control fuse: The supply indicators are healthy and the 24 V rail is dead. Prove voltage on both sides of the fuse.
- Fault 10: High-resistance solenoid terminal: A valve that chatters and measures low only while energised. Use a voltage-drop test under load.
- Fault 11: Thermal overload trip: The control supply is healthy and the contactor cannot energise. Trace the series chain to the open protective contact.
- Fault 12: Welded safety output contact: A light curtain is interrupted yet the contactor path stays continuous. Prove whether the relay output actually opens.
- Fault 13: Pt100 open compensation lead: An over-range temperature channel with a sensor-break diagnostic. Compare continuity on the three RTD conductors.
- Fault 14: Reversed thermocouple polarity: A temperature that falls as the process heats up. Verify polarity at the input card against the sensor type.
- Fault 15: Analog valve feedback drift: A valve display at 50 percent and a PLC reading consistently high. Separate wiring loss from a calibration offset.
- Fault 16: RS-485 terminator disconnected: Modbus that works slowly and fails at speed on long runs. Check end-to-end termination on the de-energised bus.
- Fault 17: VFD STO channel 1 open: The guard is closed and the drive stays inhibited. Compare both safety output channels at the relay and at the drive.
- Fault 18: Intermittent IO-Link C/Q conductor: A powered sensor that drops out when the machine vibrates. Find the conductor that only fails under movement.
- Fault 19: Load cell signal pair reversed: A weighing channel that reads backwards under load. Verify the millivolt signal pair against the transmitter.
Who this track is for
Maintenance technicians, apprentices and controls engineers who need to find why a machine stopped without swapping parts at random.
7 of the 27 units are free with a free account, with no card and no expiry. The other 20 are part of a paid plan; compare them on the pricing page.
Related tracks
- Electrical FoundationsThe electrics you need before PLC wiring: Ohm's law to a start/stop circuit, in 12 short units.12 units, 4 free
- Industrial SafetyWhy machines are guarded, how stops and interlocks work, and the safe habits that keep technicians and controls engineers out of trouble.12 units, 4 free
What is the best way to troubleshoot an industrial machine?
Work in a fixed order: confirm what the machine was asked to do, check the permissives and safety state, compare the controller input and output states with what the field device is really doing, then measure at the point where the signal is lost. Changing parts before you have a measurement that points at them is guessing.
How do I learn fault finding without breaking real equipment?
Practise on simulated machines where faults can be injected, measured and cleared as often as you like. You build the diagnostic habit first and meet real equipment afterwards, with lockout/tagout and a qualified person in place.
Is PLC troubleshooting different from electrical troubleshooting?
They overlap. PLC troubleshooting starts from the program and the I/O status and works outward to the field, while electrical troubleshooting starts from the circuit and measurements. Good technicians use both views of the same fault, which is why this track teaches them together.
How much of Troubleshooting is free?
7 of the 27 units are free with a free account, no credit card and no expiry, starting with The half-split troubleshooting method. The remaining 20 units are included with a paid plan; see the pricing page for the current plans.
Do I need a PLC or any hardware?
No. Everything runs in the browser against simulated equipment. It is training material: it does not replace supervised practice on real equipment, and lockout/tagout and a qualified person are required for real equipment.
Start with the free units
Browser-based, no install, no hardware.
Start free: The half-split troubleshooting method