Evidence to watch
The function is proved by changed behavior, not by a parameter value alone.
- Residual motor frequency
- Search/capture state
- Output current during torque pickup
Flying start—also called speed search or catch on the fly—estimates the speed and direction of an already rotating motor before the drive reapplies controlled torque.
Why it matters
Fans, pumps and high-inertia machines can still be spinning after a coast stop or supply interruption. Starting from zero frequency against that rotating field can create a current surge, torque shock or trip.
Interactive proof
Keep the motor, load and starting condition constant. Change one function at a time, then use the electrical and mechanical evidence to explain the result.
Run the motor above 25 Hz and select coast stop.
Reissue run with flying start disabled and inspect the overcurrent evidence.
Enable flying start, repeat the coast/restart sequence and compare the captured speed.
The function is proved by changed behavior, not by a parameter value alone.
These errors can make a healthy drive appear faulty or create a misleading test.
Primary technical references
This guide uses vendor-neutral terminology. For real equipment, use the manual for the installed model, option cards and firmware, plus the machine risk assessment and approved commissioning procedure.
A VFD can ramp the frequency down, remove torque and coast, use a faster quick-stop ramp, or apply DC injection braking. Each produces a different current, torque, stopping time and DC-bus response.
Read and test F-41Current limiting caps drive output current and therefore available motor torque. The drive may slow or extend acceleration instead of immediately tripping when the load demand reaches that limit.
Read and test F-20A VFD run command can come from the local keypad, hardwired terminals or a fieldbus control word. The selected source must match the signal the PLC or operator is actually sending.
Read and testFrom explanation to evidence