Technical reference and worked-example guide
Modbus function code 16 multiple-register write guide: field reference
Direct answer
The reader can bound a function 16 write, validate byte count and register quantity, avoid partial interpretation and prove the intended change with read-back and process evidence.
Written for pLC programmers writing multiword setpoints, recipes or parameters to Modbus servers.

Definition
Authorized client, server identity, function 16, starting offset, register quantity, byte count, payload order, data type, limits and write authority.
Signal path
Approved engineering value through encoding, ordered words, write request, server validation, response echo, read-back and independently observed application state.
Worked example
One bounded write changes only the documented registers and produces the expected read-back and permitted equipment response.
Limits
First and last valid address, multiword boundary, excessive quantity, illegal value, exception, timeout, duplicate request, partial gateway handling and restart.
Common mistake
An authority, identity, offset, quantity, byte-count, word-order, data-type, limit, response or application mismatch.
Verification
The change reviewed, backed up, tested in a safe environment and verified against current device documentation.
What does Modbus function code 16 do?
It writes a contiguous group of holding registers in one request and returns the accepted starting address and quantity.
How do you verify a Modbus write?
Check the response, read the affected registers back and confirm the permitted physical or application result independently.