CCST 45 — Verifying an Alarm Setpoint with Dead Band
Ready to build this?
Sign up free — no credit card required. This scenario requires the Pro plan.
Sign up to play this scenario →Already have an account? Log in
Not ready for Pro? Try a free scenario like this →
Briefing
You are loop-checking a high alarm. A calibrator simulates the process value PV_PCT (0 to 100 percent) at the transmitter. HI_ALARM: on above 80 percent, off below 75 percent, and unchanged between 75 and 80 (inclusive). That 5 percent dead band stops the alarm chattering. ALARM_VERIFIED: the loop check record. It latches only once the alarm has been seen to come ON and then seen to clear. It stays set when the value rises again. RESET_CHECK clears the record, so the check can be repeated: after a reset the alarm has to be seen to come on and clear again before it verifies. Comparisons are built with Compare boxes, or in the Code tab as contacts, for example | (A > B) | := LAMP ;
Objectives
- HI_ALARM trips above 80 percent and clears below 75 percent
- Between 75 and 80 (inclusive) the alarm keeps its state, rising and falling
- ALARM_VERIFIED latches only after the alarm has come on and then cleared
- RESET_CHECK clears the record so the check can be run again
Hints
- There are two jobs: the alarm itself, and the memory of what the technician has proven so far. Treat them separately.
- The alarm needs memory because it must hold its state between two limits. What switches it on, and what separately switches it off?
- The check record needs a second piece of memory: something that remembers the alarm has been seen on, and only counts once it has also cleared.
- Ramp 50, 85, 78, 74, then 85 again: the alarm reads off, on, on, off, on, and the record sets at 74 and stays. Then pulse RESET_CHECK.
I/O Table
Inputs
PV_PCTSimulated process value, 0-100 percent
INT · %IW0
RESET_CHECKClear the loop-check record
BOOL · %I0.0
Outputs
HI_ALARMHigh alarm
BOOL · %Q0.0
ALARM_VERIFIEDAlarm seen to come on and clear
BOOL · %Q0.1
Your program will be tested against:
All test cases run automatically when you submit. Assertions are hidden until you pass.
- #150 percent → quiet
Nothing on below the setpoint
- #285 percent → alarm on, not verified
Trips above 80
- #385 then 78 → alarm still on
Dead band holds the alarm on
- #485, 78, 74 → cleared and verified
The record sets once the alarm has come on and cleared
- #550 then 78 → still quiet
The dead band does not trip a rising value
- #6Reset clears the record
A reset starts the check again from scratch
- #7Exactly 80 and 75 hold the state
The band edges are inside the band