Basic
20 min

Lift Station — Alternating Pumps

pumpswateralternationalarmthermal
Lift Station — Alternating Pumps scenario preview

Ready to build this?

Sign up free — no credit card required. This scenario requires the Basic plan.

Sign up to play this scenario →

Already have an account? Log in

Briefing

A wet-well lift station uses two submersible pumps in alternating duty. When the wet well rises to the HIGH level, the duty pump starts; it stops when the well drains to LOW. After each completed cycle the duty assignment swaps so both pumps accumulate equal runtime. A thermal trip on the duty pump hands control to the standby pump. If both thermals trip simultaneously, or the well overflows (above HIGH for too long without draining), the ALARM_HORN and ALARM_LAMP activate.

Objectives

  • WET_WELL_HIGH starts the duty pump; WET_WELL_LOW stops it
  • Duty alternates after each completed pump cycle (HIGH → LOW)
  • PUMP1_THERMAL trips Pump 1 — standby Pump 2 takes over immediately
  • PUMP2_THERMAL trips Pump 2 — standby Pump 1 takes over immediately
  • Both thermals tripped simultaneously triggers ALARM_LAMP and ALARM_HORN
  • Tank overflow (level stays at HIGH with no working pump) triggers ALARM_LAMP and ALARM_HORN

Hints

  • Latch the pumping demand: SET a PUMP_DEMAND bit on WET_WELL_HIGH, RESET it on WET_WELL_LOW — gating on WET_WELL_HIGH alone chatters at the high float
  • Use a DUTY_IS_2 latch bit that toggles on each rising edge of WET_WELL_LOW (pump-down complete)
  • PUMP1_RUN := PUMP_DEMAND AND (NOT DUTY_IS_2 OR PUMP2_THERMAL) AND NOT PUMP1_THERMAL
  • PUMP2_RUN := PUMP_DEMAND AND (DUTY_IS_2 OR PUMP1_THERMAL) AND NOT PUMP2_THERMAL
  • ALARM := (PUMP1_THERMAL AND PUMP2_THERMAL) OR OVERFLOW_BIT
  • ALARM_LAMP := ALARM; ALARM_HORN := ALARM

I/O Table

Inputs

WET_WELL_HIGH

High level float switch (>90%)

BOOL · %I0.0

WET_WELL_LOW

Low level float switch (<20%)

BOOL · %I0.1

PUMP1_THERMAL

Pump 1 thermal overload trip

BOOL · %I0.2

PUMP2_THERMAL

Pump 2 thermal overload trip

BOOL · %I0.3

Outputs

PUMP1_RUN

Pump 1 run contactor

BOOL · %Q0.0

PUMP2_RUN

Pump 2 run contactor

BOOL · %Q0.1

ALARM_LAMP

Alarm indicator lamp

BOOL · %Q0.2

ALARM_HORN

Alarm horn / sounder

BOOL · %Q0.3

Your program will be tested against:

All test cases run automatically when you submit. Assertions are hidden until you pass.

  1. #1Pump 1 (duty) starts on WET_WELL_HIGH

    With no thermals tripped, Pump 1 starts when level rises to HIGH

  2. #2Duty pump stops on WET_WELL_LOW

    Pump 1 stops when level drains to LOW

  3. #3Duty alternates after each fill cycle

    After one complete cycle Pump 2 becomes duty

  4. #4Pump 1 thermal trip hands off to Pump 2

    PUMP1_THERMAL while Pump 1 is duty causes Pump 2 to start

  5. #5Both thermal trips activate alarm

    PUMP1_THERMAL AND PUMP2_THERMAL triggers ALARM_LAMP and ALARM_HORN

Ready to build this?

Sign up free — no credit card required. This scenario requires the Basic plan.

Sign up to play this scenario →

Already have an account? Log in

Runnable simulator field guide

Lift-station PLC scenario: implementation, evidence and troubleshooting

Direct answer

Lift-station PLC scenario becomes useful when it connects wet-well levels, hysteresis, pump availability, lead and lag policy, alternation, run feedback, minimum timing, high-high alarm, failover, manual mode and restart with level sensors through demand state and pump-selection logic to starter or drive commands, flow, changing level, run feedback and alarms, then proves repeated inflow cycles maintain level within the declared band and alternate available pump duty under normal, boundary, fault and recovery conditions. The objective is a repeatable engineering or learning result, not merely activity inside a page or tool.

This guide is written for pLC and water-process learners implementing level demand, lead-lag pumps, run feedback, high-level alarms, failover and deliberate restart. The intended result is specific: the learner can define every level transition and pump response and prove normal, failed-pump, stuck-sensor and power-return cases without uncontrolled cycling.

a browser PLC workstation connected to a guarded pump, level and conveyor training rig for repeatable control cases while studying lift-station level, pump, alarm and failover control
The scene keeps lift-station level, pump, alarm and failover control attached to declared conditions, observable results, diagnostic boundaries and evidence another person can reproduce.

System map / 02

Six concepts that control the result

Treat these as connected checkpoints. Each checkpoint has an expected state, an observable state and a boundary to the next part of the system. That structure prevents a software indication from being mistaken for physical proof.

NODE 01observable

Define the operating contract

wet-well levels, hysteresis, pump availability, lead and lag policy, alternation, run feedback, minimum timing, high-high alarm, failover, manual mode and restart. For lift-station level, pump, alarm and failover control, record the initial condition, actor, requested change, observable result and stopping condition before selecting a tool or implementation.

NODE 02observable

Map the evidence path

level sensors through demand state and pump-selection logic to starter or drive commands, flow, changing level, run feedback and alarms. Separate request, internal state, output or service, physical or user-visible result and independent feedback so each boundary can be inspected.

NODE 03observable

Prove normal operation

repeated inflow cycles maintain level within the declared band and alternate available pump duty. Run more than one cycle from a known state and retain the values, timings or artifacts that demonstrate repeatability.

NODE 04observable

Exercise a boundary case

failed lead, unavailable lag, stuck high or low sensor, rapid cycling, no-flow feedback, high-high level, manual override and power return. Choose minimum, maximum, simultaneous, delayed or restart conditions that reveal assumptions hidden by the happy path.

NODE 05observable

Diagnose a controlled fault

a level, threshold, hysteresis, selection, command, starter, pump, hydraulic, feedback, alarm or restart mismatch. Preserve the first symptom, divide the system at a measurable boundary and change one condition only after predicting the result.

NODE 06observable

Transfer and hand over

the sequence and alarm response verified with target PLC, actual instruments, pumps and approved operational procedures. Restore normal state, remove temporary changes, repeat affected checks and document which claims remain limited to the learning environment.

Procedure / 03

A six-step practice and commissioning workflow

Run the steps in order the first time. Later, the same structure becomes a diagnostic loop: define the expected condition, observe the boundary, interpret the difference and choose one proving action.

  1. 01

    Write the acceptance case

    Convert wet-well levels, hysteresis, pump availability, lead and lag policy, alternation, run feedback, minimum timing, high-high alarm, failover, manual mode and restart into initial conditions, one stimulus and observable pass criteria.

    Evidence: Another person can repeat the case without guessing the intended result.

    Avoid: Using page completion or an animation as the acceptance criterion.

  2. 02

    Build the map

    Document level sensors through demand state and pump-selection logic to starter or drive commands, flow, changing level, run feedback and alarms and name who owns each state or decision.

    Evidence: Every request and result has a source, destination and useful inspection point.

    Avoid: Using the same value as command, status and independent feedback.

  3. 03

    Run the baseline

    Apply repeated inflow cycles maintain level within the declared band and alternate available pump duty from a clean start and record the expected evidence.

    Evidence: Repeated runs produce the same bounded result.

    Avoid: Changing several parameters before a baseline exists.

  4. 04

    Challenge assumptions

    Test failed lead, unavailable lag, stuck high or low sensor, rapid cycling, no-flow feedback, high-high level, manual override and power return without changing the acceptance contract.

    Evidence: Limits, timing and restart behavior reach defined states.

    Avoid: Testing only one ideal sequence.

  5. 05

    Isolate one failure

    Introduce or analyse a level, threshold, hysteresis, selection, command, starter, pump, hydraulic, feedback, alarm or restart mismatch and locate the first disagreement.

    Evidence: The proving action distinguishes the leading hypotheses.

    Avoid: Resetting, forcing or replacing before evidence is retained.

  6. 06

    Close the evidence loop

    Complete the sequence and alarm response verified with target plc, actual instruments, pumps and approved operational procedures and repeat the affected regression cases.

    Evidence: A run is complete only when the requested behavior, stop behavior, fault response and recovery are observable from a fresh initial condition.

    Avoid: Treating an acknowledged message or one successful rerun as handover.

Diagnostic matrix / 04

Symptoms, proving points and next actions

The table is a reasoning aid, not a parts-replacement chart. Preserve the initial symptom, inspect the named boundary and use the interpretation to choose the next controlled test. Site safety procedures and equipment manuals remain authoritative.

Diagnostic symptoms, inspection points, interpretations and next actions for Lift-station PLC scenario: implementation, evidence and troubleshooting
Observed symptomInspectInterpretationNext proving action
The expected result is unclearRequirement, initial state, actor, stimulus, units and pass conditionThe operator, programmer and reviewer may be solving different versions of the task.Rewrite one observable acceptance case before continuing.
Internal state changes but the outcome does notRequest, final owner, output or service boundary and independent feedbackA software or interface indication proves intent at one layer, not the complete outcome.Trace the first boundary after the changing state.
Normal case passes but an edge case failsLimits, timing, simultaneous events, reset and restart assumptionsThe implementation contains a hidden assumption exposed by the changed condition.Add the failed boundary as a permanent regression case.
The failure disappears after resetOriginal symptom, histories, diagnostics, timestamps and active causeReset changed evidence or state without proving the initiating cause.Reproduce under a controlled condition and preserve pre/post-event data.
Simulator and target disagreeModel boundary, software version, task timing, I/O behavior, data types and configurationA learning model and the intended target do not share one of the recorded assumptions.Reduce the case and verify against current target documentation.
The result cannot be explainedPrediction, observation, proving action, alternative hypotheses and limitationsActivity occurred but the evidence is not yet transferable or reviewable.Have the learner defend the signal path and repeat a changed case.

Product evidence / 05

What the browser practice can actually demonstrate

The browser runtime joins editable control state to visible I/O and machine or process behavior, allowing the same initial conditions and stimuli to be replayed.

Where simulation stops

The modeled station cannot size a wet well, pump or pipe, predict hydraulics, validate environmental obligations, design safety or commission physical equipment.

Commissioning notebook / 06

Six cases that turn the concepts into evidence

Use these as written briefs rather than click-through instructions. For every case, state the expected condition before acting, retain the first useful observation and explain why the final result proves the requirement. A different program or component choice can still be correct when it produces the same bounded behavior and evidence.

Case 01

predict → observe → prove

Prove define the operating contract

Engineering context. wet-well levels, hysteresis, pump availability, lead and lag policy, alternation, run feedback, minimum timing, high-high alarm, failover, manual mode and restart. For lift-station level, pump, alarm and failover control, record the initial condition, actor, requested change, observable result and stopping condition before selecting a tool or implementation. Begin with a written normal condition and identify which request, state, physical result or communication value will provide independent confirmation. Do not begin by changing the configuration; the initial state is part of the evidence and should remain reproducible.

Controlled setup. Use the “Write the acceptance case” stage of the workflow: convert wet-well levels, hysteresis, pump availability, lead and lag policy, alternation, run feedback, minimum timing, high-high alarm, failover, manual mode and restart into initial conditions, one stimulus and observable pass criteria. The acceptance record should show this result: another person can repeat the case without guessing the intended result. Record initial conditions, the exact stimulus and the observation point so another learner can repeat the case without relying on your memory.

Fault challenge. Introduce or analyse “The expected result is unclear” as one bounded deviation. Inspect requirement, initial state, actor, stimulus, units and pass condition The working interpretation is that the operator, programmer and reviewer may be solving different versions of the task. The next proving action is to rewrite one observable acceptance case before continuing. Change only one condition before observing the result, and preserve timestamps or measurements where timing matters.

Review and recovery. The most common trap here is using page completion or an animation as the acceptance criterion. After restoring the cause, repeat the normal case and at least one stop, timeout, disconnect or restart boundary relevant to this topic. Remove temporary forces and bypasses, return the model to a known state and retain the evidence that both operation and recovery are deliberate.

Explain it aloud: What does a lift-station PLC control? A defensible short answer is: It commonly monitors wet-well level, starts and alternates pumps, stages demand, checks feedback and generates alarms for abnormal conditions.

Case 02

predict → observe → prove

Prove map the evidence path

Engineering context. level sensors through demand state and pump-selection logic to starter or drive commands, flow, changing level, run feedback and alarms. Separate request, internal state, output or service, physical or user-visible result and independent feedback so each boundary can be inspected. Begin with a written normal condition and identify which request, state, physical result or communication value will provide independent confirmation. Do not begin by changing the configuration; the initial state is part of the evidence and should remain reproducible.

Controlled setup. Use the “Build the map” stage of the workflow: document level sensors through demand state and pump-selection logic to starter or drive commands, flow, changing level, run feedback and alarms and name who owns each state or decision. The acceptance record should show this result: every request and result has a source, destination and useful inspection point. Record initial conditions, the exact stimulus and the observation point so another learner can repeat the case without relying on your memory.

Fault challenge. Introduce or analyse “Internal state changes but the outcome does not” as one bounded deviation. Inspect request, final owner, output or service boundary and independent feedback The working interpretation is that a software or interface indication proves intent at one layer, not the complete outcome. The next proving action is to trace the first boundary after the changing state. Change only one condition before observing the result, and preserve timestamps or measurements where timing matters.

Review and recovery. The most common trap here is using the same value as command, status and independent feedback. After restoring the cause, repeat the normal case and at least one stop, timeout, disconnect or restart boundary relevant to this topic. Remove temporary forces and bypasses, return the model to a known state and retain the evidence that both operation and recovery are deliberate.

Explain it aloud: How can pump short cycling be prevented? A defensible short answer is: Use appropriate level separation or hysteresis, minimum run and stop policies and correct hydraulic design, then test sensor and inflow boundaries.

Case 03

predict → observe → prove

Prove prove normal operation

Engineering context. repeated inflow cycles maintain level within the declared band and alternate available pump duty. Run more than one cycle from a known state and retain the values, timings or artifacts that demonstrate repeatability. Begin with a written normal condition and identify which request, state, physical result or communication value will provide independent confirmation. Do not begin by changing the configuration; the initial state is part of the evidence and should remain reproducible.

Controlled setup. Use the “Run the baseline” stage of the workflow: apply repeated inflow cycles maintain level within the declared band and alternate available pump duty from a clean start and record the expected evidence. The acceptance record should show this result: repeated runs produce the same bounded result. Record initial conditions, the exact stimulus and the observation point so another learner can repeat the case without relying on your memory.

Fault challenge. Introduce or analyse “Normal case passes but an edge case fails” as one bounded deviation. Inspect limits, timing, simultaneous events, reset and restart assumptions The working interpretation is that the implementation contains a hidden assumption exposed by the changed condition. The next proving action is to add the failed boundary as a permanent regression case. Change only one condition before observing the result, and preserve timestamps or measurements where timing matters.

Review and recovery. The most common trap here is changing several parameters before a baseline exists. After restoring the cause, repeat the normal case and at least one stop, timeout, disconnect or restart boundary relevant to this topic. Remove temporary forces and bypasses, return the model to a known state and retain the evidence that both operation and recovery are deliberate.

Explain it aloud: What should I learn first about lift-station level, pump, alarm and failover control? A defensible short answer is: Start with the operating contract and evidence path: wet-well levels, hysteresis, pump availability, lead and lag policy, alternation, run feedback, minimum timing, high-high alarm, failover, manual mode and restart, followed by level sensors through demand state and pump-selection logic to starter or drive commands, flow, changing level, run feedback and alarms. Add advanced features only after the baseline is predictable.

Case 04

predict → observe → prove

Prove exercise a boundary case

Engineering context. failed lead, unavailable lag, stuck high or low sensor, rapid cycling, no-flow feedback, high-high level, manual override and power return. Choose minimum, maximum, simultaneous, delayed or restart conditions that reveal assumptions hidden by the happy path. Begin with a written normal condition and identify which request, state, physical result or communication value will provide independent confirmation. Do not begin by changing the configuration; the initial state is part of the evidence and should remain reproducible.

Controlled setup. Use the “Challenge assumptions” stage of the workflow: test failed lead, unavailable lag, stuck high or low sensor, rapid cycling, no-flow feedback, high-high level, manual override and power return without changing the acceptance contract. The acceptance record should show this result: limits, timing and restart behavior reach defined states. Record initial conditions, the exact stimulus and the observation point so another learner can repeat the case without relying on your memory.

Fault challenge. Introduce or analyse “The failure disappears after reset” as one bounded deviation. Inspect original symptom, histories, diagnostics, timestamps and active cause The working interpretation is that reset changed evidence or state without proving the initiating cause. The next proving action is to reproduce under a controlled condition and preserve pre/post-event data. Change only one condition before observing the result, and preserve timestamps or measurements where timing matters.

Review and recovery. The most common trap here is testing only one ideal sequence. After restoring the cause, repeat the normal case and at least one stop, timeout, disconnect or restart boundary relevant to this topic. Remove temporary forces and bypasses, return the model to a known state and retain the evidence that both operation and recovery are deliberate.

Explain it aloud: How do I practise lift-station level, pump, alarm and failover control effectively? A defensible short answer is: Use short cases with known initial conditions, a written prediction, one action and an observable result. Then alter a boundary or fault and explain why the evidence changed.

Case 05

predict → observe → prove

Prove diagnose a controlled fault

Engineering context. a level, threshold, hysteresis, selection, command, starter, pump, hydraulic, feedback, alarm or restart mismatch. Preserve the first symptom, divide the system at a measurable boundary and change one condition only after predicting the result. Begin with a written normal condition and identify which request, state, physical result or communication value will provide independent confirmation. Do not begin by changing the configuration; the initial state is part of the evidence and should remain reproducible.

Controlled setup. Use the “Isolate one failure” stage of the workflow: introduce or analyse a level, threshold, hysteresis, selection, command, starter, pump, hydraulic, feedback, alarm or restart mismatch and locate the first disagreement. The acceptance record should show this result: the proving action distinguishes the leading hypotheses. Record initial conditions, the exact stimulus and the observation point so another learner can repeat the case without relying on your memory.

Fault challenge. Introduce or analyse “Simulator and target disagree” as one bounded deviation. Inspect model boundary, software version, task timing, I/O behavior, data types and configuration The working interpretation is that a learning model and the intended target do not share one of the recorded assumptions. The next proving action is to reduce the case and verify against current target documentation. Change only one condition before observing the result, and preserve timestamps or measurements where timing matters.

Review and recovery. The most common trap here is resetting, forcing or replacing before evidence is retained. After restoring the cause, repeat the normal case and at least one stop, timeout, disconnect or restart boundary relevant to this topic. Remove temporary forces and bypasses, return the model to a known state and retain the evidence that both operation and recovery are deliberate.

Explain it aloud: What counts as proof of competence? A defensible short answer is: A repeatable artifact or system result plus an explanation of the signal path is stronger than time spent, screenshots or a copied answer. Physical competence requires separate supervised evidence.

Case 06

predict → observe → prove

Prove transfer and hand over

Engineering context. the sequence and alarm response verified with target PLC, actual instruments, pumps and approved operational procedures. Restore normal state, remove temporary changes, repeat affected checks and document which claims remain limited to the learning environment. Begin with a written normal condition and identify which request, state, physical result or communication value will provide independent confirmation. Do not begin by changing the configuration; the initial state is part of the evidence and should remain reproducible.

Controlled setup. Use the “Close the evidence loop” stage of the workflow: complete the sequence and alarm response verified with target plc, actual instruments, pumps and approved operational procedures and repeat the affected regression cases. The acceptance record should show this result: a run is complete only when the requested behavior, stop behavior, fault response and recovery are observable from a fresh initial condition. Record initial conditions, the exact stimulus and the observation point so another learner can repeat the case without relying on your memory.

Fault challenge. Introduce or analyse “The result cannot be explained” as one bounded deviation. Inspect prediction, observation, proving action, alternative hypotheses and limitations The working interpretation is that activity occurred but the evidence is not yet transferable or reviewable. The next proving action is to have the learner defend the signal path and repeat a changed case. Change only one condition before observing the result, and preserve timestamps or measurements where timing matters.

Review and recovery. The most common trap here is treating an acknowledged message or one successful rerun as handover. After restoring the cause, repeat the normal case and at least one stop, timeout, disconnect or restart boundary relevant to this topic. Remove temporary forces and bypasses, return the model to a known state and retain the evidence that both operation and recovery are deliberate.

Explain it aloud: Why test faults and restart behavior? A defensible short answer is: Because a level, threshold, hysteresis, selection, command, starter, pump, hydraulic, feedback, alarm or restart mismatch or failed lead, unavailable lag, stuck high or low sensor, rapid cycling, no-flow feedback, high-high level, manual override and power return can expose assumptions that never appear during ideal startup and steady operation.

Answer surface / 07

Questions people ask about Lift-station PLC scenario

These concise answers define the operating, training and product boundaries most often missed in broad summaries. The full workflow and diagnostic table above provide the evidence behind them.

What does a lift-station PLC control?

It commonly monitors wet-well level, starts and alternates pumps, stages demand, checks feedback and generates alarms for abnormal conditions.

How can pump short cycling be prevented?

Use appropriate level separation or hysteresis, minimum run and stop policies and correct hydraulic design, then test sensor and inflow boundaries.

What should I learn first about lift-station level, pump, alarm and failover control?

Start with the operating contract and evidence path: wet-well levels, hysteresis, pump availability, lead and lag policy, alternation, run feedback, minimum timing, high-high alarm, failover, manual mode and restart, followed by level sensors through demand state and pump-selection logic to starter or drive commands, flow, changing level, run feedback and alarms. Add advanced features only after the baseline is predictable.

How do I practise lift-station level, pump, alarm and failover control effectively?

Use short cases with known initial conditions, a written prediction, one action and an observable result. Then alter a boundary or fault and explain why the evidence changed.

What counts as proof of competence?

A repeatable artifact or system result plus an explanation of the signal path is stronger than time spent, screenshots or a copied answer. Physical competence requires separate supervised evidence.

Why test faults and restart behavior?

Because a level, threshold, hysteresis, selection, command, starter, pump, hydraulic, feedback, alarm or restart mismatch or failed lead, unavailable lag, stuck high or low sensor, rapid cycling, no-flow feedback, high-high level, manual override and power return can expose assumptions that never appear during ideal startup and steady operation.

Can browser practice replace official software or hardware?

No. It can build concepts and diagnostic reasoning. Exact firmware, I/O electrical behavior, networking, safety and commissioning require current official tools, documentation and target equipment.

How should progress be documented?

Keep the requirement, initial state, program or configuration, observed values, fault hypothesis, proving action, recovery result and a concise limitations statement.