Motor 02 — Remember the trip

Briefing

A trip must not be forgotten the moment the cause goes away. When ESTOP or THERMAL_OL goes active, the motor stops and FAULT_LAMP lights, and both stay that way after the cause clears. START is ignored while the fault is on. RESET_PB clears the fault, but only when ESTOP and THERMAL_OL are both FALSE. Resetting never restarts the motor: the operator presses START again.

Objectives

  • ESTOP or THERMAL_OL active: MOTOR and RUN_LAMP off, FAULT_LAMP on
  • The fault stays on after the cause clears
  • RESET_PB clears the fault only when ESTOP and THERMAL_OL are both FALSE
  • START does nothing while the fault is on; it works again after a reset

Hints

  • FAULT_LAMP must outlive ESTOP and THERMAL_OL. Use the spare memory bit FAULT to remember that a trip happened, then show it on the lamp.
  • What switches the memory on? Either cause going active. What switches it off? RESET_PB, but never while a cause is still active.
  • The motor must also respect the memory: it stops when the fault is on, and START cannot start it while the fault is on.
  • Internal bits update one scan later than outputs. If a check looks one moment too early, nothing is wrong with your logic.

I/O Table

Inputs

START_PB

Start push-button (momentary NO)

BOOL · %I0.0

STOP_PB

Stop push-button (TRUE = pressed)

BOOL · %I0.1

ESTOP

Emergency stop (TRUE = active)

BOOL · %I0.2

THERMAL_OL

Thermal overload relay (TRUE = tripped)

BOOL · %I0.3

RESET_PB

Fault reset push-button (TRUE = pressed)

BOOL · %I0.4

Outputs

MOTOR

Motor contactor

BOOL · %Q0.0

RUN_LAMP

Running lamp

BOOL · %Q0.1

FAULT_LAMP

Fault lamp (stays on until reset)

BOOL · %Q0.2

Your program will be tested against:

All test cases run automatically when you submit. Assertions are hidden until you pass.

  1. #1ESTOP while running → motor off, FAULT_LAMP on

    The trip drops the motor and RUN_LAMP and lights the fault lamp

  2. #2ESTOP released → FAULT_LAMP stays on, motor stays off

    A remembered trip does not clear itself

  3. #3RESET while THERMAL_OL is still active → fault stays on

    A reset is refused while a cause is still present

  4. #4Cause cleared, then RESET → FAULT_LAMP off, motor still off

    Resetting clears the fault without restarting the motor

  5. #5START while the fault is latched → motor stays off

    ESTOP has cleared but the fault is still on, so START does nothing

  6. #6After a reset, START runs the motor again

    The full recovery: trip, clear, reset, start

  7. #7RESET while ESTOP is still active → fault stays on

    The emergency stop is a cause too: no reset while it is held