Fault 4 — Broken +24 V Supply Wire to the PLC

What you'll learn

**Symptom:** the morning shift calls — the panel won't power up. You walk over: the PSU indicator LED is on, but the PLC base is completely dark. None of the input or output LEDs are lit; nothing on the panel responds.

Lab time: ~6 minutes.

Lesson briefing

Broken +24 V Supply Wire to the PLC

Symptom: the morning shift calls — the panel won't power up. You walk over: the PSU indicator LED is on, but the PLC base is completely dark. None of the input or output LEDs are lit; nothing on the panel responds.

The PSU is fine. Something between the PSU and the PLC has gone open — most likely a wire that's worked loose at a terminal screw, or a broken strand at a ferrule. There's no scorching, no smell, no tripped breaker — just silence.

Reach for the multimeter on the toolbar. Voltage mode is your friend here. Walk the +24 V rail from upstream to downstream: confirm the supply is healthy at the PSU output, then keep probing toward the PLC until the voltage disappears. The break sits between your last "good" reading and your first "OL". Continuity mode is the secondary check — once you suspect a segment, probe its two ends for a beep that should be there but isn't.

Hints

Hint 1

Start at the PSU output. Probe across the +V and 0V terminals in voltage mode — confirm the supply itself is alive (you should read +24 V).

Hint 2

Sign up to unlock the full hint sequence.

Hint 3

Sign up to unlock the full hint sequence.

Hint 4

Sign up to unlock the full hint sequence.

This lesson uses 5 placed components on the lab canvas. Components are vendor-neutral (no proprietary trademarks); the wiring rules apply to any equivalent industrial part.

Sign up free to start

This foundation lab is included on Free — sign up takes a minute.

Sign up free to start →

You might also like

Competency and practice field guide

Broken PLC supply-wire fault lesson: practice plan

Direct answer

The learner can predict node voltages, choose a valid reference and locate the first point where expected supply no longer continues without unsafe part swapping.

Written for electrical and controls learners diagnosing a PLC or I/O branch that has lost its positive supply conductor.

a touch-safe 24 VDC troubleshooting bench with protection, terminal blocks, PLC I/O, test points and a visible open conductor while studying broken 24 VDC supply-conductor diagnosis using voltage, reference and load-aware evidence
System map / 02

NODE 01observable

Scope

Source, protective device, positive conductor, return conductor, terminals, branch load, PLC power state, input or output supply and approved test points.

NODE 02observable

Signal path

Supply energy from source through protection and conductors into PLC or I/O load, reference return, device indication and controller diagnostic state.

NODE 03observable

Baseline practice

Expected voltage at each named node under a known connected load with the PLC and field branch reaching their declared healthy state.

NODE 04observable

Edge cases

High-resistance break, backfeed, floating reference, open return, blown protection, disconnected branch, intermittent conductor and restored power.

NODE 05observable

Fault practice

A source, protection, positive path, terminal, branch, load, return-reference or controller-power mismatch.

NODE 06observable

Transfer to the job

The cause repaired, conductors secured, temporary test changes removed and startup plus affected I/O cases repeated under procedure.

Answer surface / 07

How do you find a broken 24 V wire to a PLC?

Use the current schematic and a stated reference, predict voltage at successive approved nodes, then locate the first boundary where voltage under load no longer matches the prediction.

Can a meter show 24 V through a broken supply?

A high-impedance meter may show misleading ghost or backfed voltage in some circuits. Compare under the permitted test method and verify the return path and load condition.