Fault 6
Pro

Fault 6 — Broken Signal Wire Between Photoeye and PLC

What you'll learn

**Symptom:** the line operator reports the conveyor isn't indexing — the PLC isn't reacting to the photoeye on the infeed. You walk over to the panel.

Lab time: ~8 minutes.

Lesson briefing

Broken Signal Wire Between Photoeye and PLC

Symptom: the line operator reports the conveyor isn't indexing — the PLC isn't reacting to the photoeye on the infeed. You walk over to the panel.

The photoeye's own status LED is on. There's a target in front of it; the sensor is detecting and its output is driving. But the PLC's X0 input LED is dark — the input the sensor feeds into is reading low. The sensor works; the PLC's input circuit works; something between them doesn't.

Reach for the multimeter on the toolbar. Voltage mode is your friend here, but the trick is to probe BOTH SIDES of the signal wire. A signal wire that's broken in the middle has a clean diagnostic asymmetry: the sensor end is still energised (the PNP output is internally driving +V to its signal pin), but the PLC end is electrically floating. Put the black probe on the panel 0 V rail and walk the red probe along the signal path: the reading you get tells you which side of the break you're on.

Continuity mode is the secondary check — once you suspect the signal wire, probe its two ends for a beep that should be there but isn't.

Hints

Hint 1

Start at the PLC. With the multimeter in voltage mode, put the black probe on the panel 0 V rail (PSU 0V or PLC 0V — same node) and red on PLC X0. On a healthy panel with the sensor detecting, you'd read +24 V there. What do you actually read?

Hint 2

Sign up to unlock the full hint sequence.

Hint 3

Sign up to unlock the full hint sequence.

Hint 4

Sign up to unlock the full hint sequence.

This lesson uses 6 placed components on the lab canvas. Components are vendor-neutral (no proprietary trademarks); the wiring rules apply to any equivalent industrial part.

Sign up to preview

Create a free account to preview this Pro lab; upgrade to open the interactive circuit.

Sign up to preview →

You might also like

Competency and practice field guide

Broken sensor-signal wire fault lesson: practice plan

Direct answer

The learner can prove the field condition and sensor output, locate the open conductor or terminal and verify tag and machine recovery.

Written for maintenance learners tracing a powered, detecting sensor whose state never reaches the controller.

an isolated low-energy electrical controls bench with PLC I/O, protective devices and measurement points used for supervised fault diagnosis while studying open sensor-signal conductor diagnosis from device output to PLC input
System map / 02

NODE 01observable

Scope

Field condition, sensor power and indication, output conductor, junction and terminal points, input channel, common reference, module indication and software tag.

NODE 02observable

Signal path

Target through sensor state and output voltage or current, cable, terminal boundaries, module electronics, process image and consuming logic.

NODE 03observable

Baseline practice

A controlled target changes sensor, terminal, channel and tag evidence together and the affected machine function responds correctly.

NODE 04observable

Edge cases

Intermittent conductor, loose terminal, wrong wire number, short to supply, short to common, shared input, leakage, wrong channel and forced tag.

NODE 05observable

Fault practice

A target, sensor, output, conductor, terminal, common, input, tag or consumer mismatch.

NODE 06observable

Transfer to the job

The conductor repair inspected and tested under approved wiring, labeling and functional-proving procedures.

Answer surface / 07

How do you find a broken sensor signal wire?

Prove sensor output at the device, then compare the same referenced signal at successive terminal and input boundaries until the first loss is located.

Why can the sensor LED be on but the PLC input off?

The sensor can detect correctly while its output type, signal conductor, common, input channel or software mapping is open or incompatible.