**Symptom:** the line operator reports the conveyor isn't indexing — the PLC isn't reacting to the photoeye on the infeed. You walk over to the panel.
Lab time: ~8 minutes.
Lesson briefing
Broken Signal Wire Between Photoeye and PLC
Symptom: the line operator reports the conveyor isn't indexing — the PLC isn't reacting to the photoeye on the infeed. You walk over to the panel.
The photoeye's own status LED is on. There's a target in front of it; the sensor is detecting and its output is driving. But the PLC's X0 input LED is dark — the input the sensor feeds into is reading low. The sensor works; the PLC's input circuit works; something between them doesn't.
Reach for the multimeter on the toolbar. Voltage mode is your friend here, but the trick is to probe BOTH SIDES of the signal wire. A signal wire that's broken in the middle has a clean diagnostic asymmetry: the sensor end is still energised (the PNP output is internally driving +V to its signal pin), but the PLC end is electrically floating. Put the black probe on the panel 0 V rail and walk the red probe along the signal path: the reading you get tells you which side of the break you're on.
Continuity mode is the secondary check — once you suspect the signal wire, probe its two ends for a beep that should be there but isn't.
Hints
Start at the PLC. With the multimeter in voltage mode, put the black probe on the panel 0 V rail (PSU 0V or PLC 0V — same node) and red on PLC X0. On a healthy panel with the sensor detecting, you'd read +24 V there. What do you actually read?
Sign up to unlock the full hint sequence.
Sign up to unlock the full hint sequence.
Sign up to unlock the full hint sequence.
Sign up to unlock the full hint sequence.
This lesson uses 6 placed components on the lab canvas. Components are vendor-neutral (no proprietary trademarks); the wiring rules apply to any equivalent industrial part.
Sign up to preview
Create a free account to preview this Pro lab; upgrade to open the interactive circuit.
Sign up to preview →