Briefing

During maintenance, a LOTO_KEY switch must disable all motion outputs. Write the interlock so that CONVEYOR_FWD can only run when LOTO_KEY is FALSE (energy isolated).

Objectives

  • CONVEYOR_FWD is blocked whenever LOTO_KEY is TRUE
  • Normal start/stop logic still works when LOTO_KEY is FALSE

Hints

  • Series LOTO_KEY (as NC contact / NOT LOTO_KEY) in the CONVEYOR_FWD rung
  • CONVEYOR_FWD := (START OR CONVEYOR_FWD) AND NOT STOP AND NOT LOTO_KEY

I/O Table

Inputs

START

Start push-button

BOOL · %I0.0

STOP

Stop push-button

BOOL · %I0.1

LOTO_KEY

LOTO key switch (TRUE=locked out)

BOOL · %I0.2

Outputs

CONVEYOR_FWD

Conveyor forward drive

BOOL · %Q0.0

Your program will be tested against:

All test cases run automatically when you submit. Assertions are hidden until you pass.

  1. #1Conveyor runs normally

    Conveyor runs normally

  2. #2LOTO key blocks start

    LOTO key blocks start

Ready to build this?

Sign up free — no credit card required. This scenario requires the Pro plan.

Sign up to play this scenario →

Already have an account? Log in

Job-readiness and assessment field guide

CCST practical 025 assessment: readiness checklist

Direct answer

The candidate can distinguish command, output signal, actuator position and process effect, then isolate a failure with one safe proving action.

Written for controls candidates tracing a controller output through interface equipment to a valve, drive or actuator and process response.

a controls technician completing a supervised practical assessment on generic PLC, motor-control and instrumentation equipment while studying final-control-element command, feedback and control-loop fault diagnosis
System map / 02

NODE 01observable

Role scope

Controller mode, output demand, limit, signal type, interface, final element, utility supply, position feedback, process response and acceptance tolerance.

NODE 02observable

Skills map

Control decision through output scaling, module, loop or network, actuator conversion, mechanical movement, process change and independent feedback.

NODE 03observable

Core exercise

Bounded output changes produce correct signal direction, final-element travel and coherent process response.

NODE 04observable

Stretch case

Manual mode, output saturation, lost air, sticky valve, reversed action, failed feedback, interlock, restart and command-source conflict.

NODE 05observable

Troubleshooting

A controller, limit, output, interface, utility, actuator, mechanics, feedback or process mismatch.

NODE 06observable

Portfolio evidence

The result documented and reviewed under current site procedure and certification-body objectives.

Answer surface / 07

How do you prove a final-control-element fault?

Compare controller demand, physical output signal, actuator indication, measured position and process response; the first disagreement narrows the fault boundary.

Can valve position feedback prove the process changed?

No. It proves a position boundary. Flow, pressure, temperature or another independent process measurement is needed when process outcome matters.