Fault 1 — Photoeye Polarity Reversal

What you'll learn

Welcome to fault-finding. From here on every lesson hands you a pre-wired panel with a problem buried in it; your job is to find the fault using the multimeter on the toolbar.

Lab time: ~8 minutes.

Lesson briefing

Photoeye Polarity Reversal

Welcome to fault-finding. From here on every lesson hands you a pre-wired panel with a problem buried in it; your job is to find the fault using the multimeter on the toolbar.

The multimeter has two probes — red and black. Pick a mode:

  • Voltage (DC): reads the DC voltage at the red probe relative to the black probe. A correctly-powered 24 VDC bus reads +24 V at a red-on-(+V) / black-on-(0V) probe; reverse the probes and you read -24 V.
  • Continuity: beeps when the two probes sit on terminals that are electrically joined. Useful for tracing wires and checking for breaks.

Symptom: the line operator reports the photoeye on the conveyor infeed has stopped detecting boxes. You walk over to the panel: the sensor LED is dark, the PLC input X0 LED is dark, and the rest of the panel looks healthy. The PSU's own indicator LED is on.

Probe the panel, decide what's wrong, then submit a diagnosis.

Hints

Hint 1

Start at the photoeye. Probe across its V+ and 0V terminals with the multimeter in voltage mode — what reading would you expect on a healthy install?

Hint 2

Sign up to unlock the full hint sequence.

This lesson uses 6 placed components on the lab canvas. Components are vendor-neutral (no proprietary trademarks); the wiring rules apply to any equivalent industrial part.

Sign up free to start

This foundation lab is included on Free — sign up takes a minute.

Sign up free to start →

You might also like

Competency and practice field guide

Photoeye polarity fault lesson: practice plan

Direct answer

The learner can verify supply polarity, sensor indication, output type, module common and tag state in order without adjusting logic prematurely.

Written for automation maintenance learners diagnosing a sensor that will not power or switch the intended PLC input.

an isolated low-energy electrical controls bench with PLC I/O, protective devices and measurement points used for supervised fault diagnosis while studying DC photoeye polarity, output type, input compatibility and signal-path diagnosis
System map / 02

NODE 01observable

Scope

Sensor voltage range, brown and blue supply conductors, polarity, black output conductor, PNP or NPN type, normally open or closed behavior, input common and target condition.

NODE 02observable

Signal path

Physical target through optical detection, sensor electronics, output conductor, module input circuit, channel indication and software tag.

NODE 03observable

Baseline practice

The correctly powered compatible sensor changes device, module and tag state together for a controlled target presentation.

NODE 04observable

Edge cases

Reversed supply, missing common, incompatible output, dark-on versus light-on, misalignment, contamination, shorted output, leakage and wrong tag.

NODE 05observable

Fault practice

A target, optical, supply, polarity, configuration, output-type, common, input-channel or software mismatch.

NODE 06observable

Transfer to the job

The target installation checked against exact sensor and module diagrams under approved procedures.

Answer surface / 07

What happens if a DC photoeye polarity is reversed?

Many protected sensors remain off, while others may be damaged or behave unpredictably; remove power and verify the exact wiring diagram before correction.

How do you separate a photoeye fault from a PLC input fault?

Compare target state, sensor indication, output voltage or current, module LED and software tag at successive boundaries.