← Back to all lessons
Wiring 7
Pro

Wiring 7 — PLC Analog Output Driving a VFD Speed Reference

What you'll learn

A **Variable Frequency Drive** (VFD) controls the speed of a 3-phase induction motor by varying the frequency and voltage of the AC power it delivers to the motor windings. This replaces mechanical speed-control methods (gearboxes, belt drives, throttling valves) with an electronic solution that is more precise, more energy-efficient, and easier to integrate with a PLC.

Lab time: ~15 minutes.

Lesson briefing

PLC Analog Output Driving a VFD Speed Reference

A Variable Frequency Drive (VFD) controls the speed of a 3-phase induction motor by varying the frequency and voltage of the AC power it delivers to the motor windings. This replaces mechanical speed-control methods (gearboxes, belt drives, throttling valves) with an electronic solution that is more precise, more energy-efficient, and easier to integrate with a PLC.

On variable-torque loads such as pumps and fans, motor speed and power draw are related by the affinity laws: reducing speed to 80 % reduces power consumption to roughly 51 % (the cube law). VFDs are therefore the single most impactful energy-saving measure in most facilities.

0-10 V vs 4-20 mA speed references

Most VFDs accept either a 0-10 V voltage reference or a 4-20 mA current reference at their analog input. The choice is usually made via a jumper or parameter on the VFD itself. This lesson uses voltage: 0 V commands 0 % speed, 10 V commands 100 % speed (maximum frequency). Current references are preferable on long cable runs where voltage drop could introduce error — the same reason 4-20 mA dominates in process instrumentation. For a panel-mount VFD reachable by a short cable run, 0-10 V is entirely appropriate.

The signal-and-common pair

The 0-10 V signal is measured as a differential voltage between the analog input terminal (terminal 2 on this VFD) and the analog common (terminal 5). Both wires must run in the same cable — ideally a twisted pair — so that any noise induced on the cable affects both conductors equally and cancels at the VFD's differential input.

Never route the signal wire alone and rely on a separate common wire routed by a different path. The common wire carries the return current for the signal; separating them creates a loop that acts as an antenna.

Single-point shield grounding

Instrument cable shields must connect to earth at one end only. In this topology the PLC analog output card is the signal source, so the shield terminates at the card's SHIELD terminal. The VFD end of the shield stays floating (unterminated or taped back). Grounding both ends would create a ground loop: small potential differences between the two earth points drive a circulating current through the shield, which couples directly into the signal pair as noise.

PE bonding — VFD and motor separately

Both the VFD chassis and the motor frame must be bonded to protective earth (PE), but they are wired as separate bonds to the cabinet ground bar — not daisy-chained. Each bond provides an independent low- impedance fault-current return path. Industrial safety practice requires that removing one item of equipment does not break the earth continuity of another.

Out of scope

VFD parameter setup (acceleration/deceleration ramps, motor nameplate data, P-code configuration) is a commissioning concern, not a wiring concern. This lesson covers the cable connections only.

Hints

Hint 1

Start with the DC distribution buses exactly as in earlier lessons: psu-1.+V → tb-24v.t0, psu-1.0V → tb-0v.t0, psu-1.PE → gnd-bar.pe0. Then supply the PLC base from t1 on each bus and the analog output card from t2 on each bus.

Hint 2

Sign up to unlock the full hint sequence.

Hint 3

Sign up to unlock the full hint sequence.

Hint 4

Sign up to unlock the full hint sequence.

This lesson uses 10 placed components on the lab canvas. Components are vendor-neutral (no proprietary trademarks); the wiring rules apply to any equivalent industrial part.

Sign up to preview

Create a free account to preview this Pro lab; upgrade to open the interactive circuit.

Sign up to preview →

You might also like

Competency and practice field guide

PLC analog-output wiring lesson: practice plan

Direct answer

The learner can map an engineering command to raw output and measured loop signal, then isolate range, reference, load, polarity and scaling errors.

Written for pLC and instrumentation learners connecting analog outputs to valves, drives, indicators or controllers with correct references and engineering units.

a technician tracing realistic industrial sensors, signal wiring, PLC inputs and measured trends at an instrumentation learning bench while studying PLC current and voltage output wiring, scaling and load evidence
System map / 02

NODE 01observable

Scope

Required function, 0–10 V or 4–20 mA range, source or sink behavior, loop power, common, channel isolation, receiver impedance, raw counts, engineering units and fail state.

NODE 02observable

Signal path

Engineering request through limit and scaling logic, output register, D/A channel, terminals, current or voltage signal, receiver interpretation and physical response.

NODE 03observable

Baseline practice

Low, midpoint and high commands produce measured signals and receiving-device results within declared tolerance.

NODE 04observable

Edge cases

Open load, short, reversed polarity, wrong range, shared common, excessive burden, underrange, overrange, lost controller power and restart.

NODE 05observable

Fault practice

A command, limit, scaling, data-type, configuration, output-channel, loop, receiver or process-response mismatch.

NODE 06observable

Transfer to the job

The loop proven with current module and receiver data plus approved measurement equipment.

Answer surface / 07

How is a PLC analog output wired?

Follow the exact module mode and receiver circuit: voltage and current outputs use different reference, load and power arrangements, so the manufacturer diagrams govern.

How do I scale a PLC analog output?

Map bounded engineering units to the module raw range, clamp invalid requests and verify low, midpoint and high points with an independent measurement.