← Back to all lessons
Wiring 15
Pro

Wiring 15 — RS-485 Modbus RTU Drop

What you'll learn

**RS-485** is the physical-layer standard used by Modbus RTU — the most widely deployed fieldbus protocol in industrial automation. You will encounter it on flow meters, temperature transmitters, variable speed drives, and PLCs from virtually every vendor.

Lab time: ~16 minutes.

Lesson briefing

RS-485 Modbus RTU Drop

RS-485 is the physical-layer standard used by Modbus RTU — the most widely deployed fieldbus protocol in industrial automation. You will encounter it on flow meters, temperature transmitters, variable speed drives, and PLCs from virtually every vendor.

Three rules you must know

1. Polarity matters RS-485 uses a differential pair: A (non-inverting, DATA+) and B (inverting, DATA−). Every device on the bus must connect A to A and B to B. Swapping A and B on even one device reverses the idle polarity for all devices — communication stops for the whole bus, not just the swapped device.

2. Termination prevents reflections At each physical end of the bus a 120 Ω termination resistor must be placed across A and B. Without it, high-frequency signal edges bounce back along the cable and corrupt waveforms. At 9 600 baud the reflections are usually tolerable; above 19 200 baud they often cause frame errors. In this lab an RS485Terminator module is placed at the far end of the drop (the PLC's built-in termination covers the near end).

3. Bus topology, not star RS-485 is a daisy-chain bus. Each device connects in line along the cable: PLC → device 1 → device 2 → terminator. A star topology (one master connected to multiple separate spurs) creates impedance mismatches that corrupt fast Modbus polling and is prohibited by the RS-485 standard.

What to wire

  1. Seed +24 V and 0 V buses from the PSU. Power the PLC from the bus.
  2. PLC comms: plc-1.X0 (DATA+ proxy) → tb-rs485-a.t0 and plc-1.X1 (DATA− proxy) → tb-rs485-b.t0.
  3. Distribute the bus: tb-rs485-a.t1 → slave-1.A and tb-rs485-b.t1 → slave-1.B (A to A, B to B — polarity!).
  4. Terminate the bus: tb-rs485-a.t2 → term-1.A and tb-rs485-b.t2 → term-1.B (terminator at the far end).
  5. Power and earth the Modbus slave: tb-24v.t2 → slave-1.+24V; tb-0v.t2 → slave-1.0V; slave-1.PE → gnd-bar.pe2.
  6. PE bonds: psu-1.PE → gnd-bar.pe0; psu-1.0V → gnd-bar.pe1.

Hints

Hint 1

Start with power distribution: psu-1.+V → tb-24v.t0 and psu-1.0V → tb-0v.t0. Power the PLC: tb-24v.t1 → plc-1.+24V and tb-0v.t1 → plc-1.0V.

Hint 2

Sign up to unlock the full hint sequence.

Hint 3

Sign up to unlock the full hint sequence.

Hint 4

Sign up to unlock the full hint sequence.

Hint 5

Sign up to unlock the full hint sequence.

Hint 6

Sign up to unlock the full hint sequence.

This lesson uses 10 placed components on the lab canvas. Components are vendor-neutral (no proprietary trademarks); the wiring rules apply to any equivalent industrial part.

Sign up to preview

Create a free account to preview this Pro lab; upgrade to open the interactive circuit.

Sign up to preview →

You might also like

Competency and practice field guide

RS-485 Modbus RTU bus wiring lesson: practice plan

Direct answer

The learner can draw the trunk and drops, identify both ends, verify reference and polarity assumptions and separate electrical-layer evidence from serial and Modbus settings.

Written for industrial communications learners wiring and diagnosing a multidrop RS-485 network used for Modbus RTU.

an industrial communications bench joining a PLC, managed Ethernet switch, remote I/O and an inspectable RS-485 multidrop segment while studying RS-485 trunk topology, polarity, termination, bias, shielding and Modbus RTU evidence
System map / 02

NODE 01observable

Scope

Two-wire or four-wire mode, trunk, drop length, A and B convention, signal reference, shield, termination, bias, baud, parity, node address and master role.

NODE 02observable

Signal path

Physical pair and reference through transceivers, serial framing and timing into Modbus request, addressed response, CRC and application register meaning.

NODE 03observable

Baseline practice

One master polling unique nodes with stable idle state, clean frames and correct register values at the declared operating rate.

NODE 04observable

Edge cases

Reversed pair, missing reference, star topology, extra termination, duplicate address, mismatched parity, noise, timeout, bus contention and restart.

NODE 05observable

Fault practice

A cable, topology, polarity, reference, termination, bias, serial-setting, address, protocol or application mismatch.

NODE 06observable

Transfer to the job

The bus inspected and tested with exact device requirements, installation practices, captured frames and representative operating conditions.

Answer surface / 07

Where should RS-485 termination resistors go?

For a typical linear multidrop bus, termination belongs at the two physical ends of the trunk, not at every device. Exact values and exceptions come from the transceiver and device documentation.

Is A always positive and B always negative on RS-485?

Naming conventions vary between vendors. Do not trust letters alone; compare the device documentation and measured or captured idle/data behavior.