Wiring 22 — Three-Wire Pt100 RTD

What you'll learn

Terminate a three-wire Pt100 resistance temperature detector on a dedicated PLC temperature input. The single A conductor lands on RTD-A; the two same-colour compensation conductors land on RTD-B1 and RTD-B2.

Lab time: ~16 minutes.

Lesson briefing

Three-Wire Pt100 RTD

Terminate a three-wire Pt100 resistance temperature detector on a dedicated PLC temperature input. The single A conductor lands on RTD-A; the two same-colour compensation conductors land on RTD-B1 and RTD-B2.

The device in the real world

Pt100 resistance sensors are common in food, HVAC and process plants because they are accurate and stable. The sensing element is a platinum resistor that is 100 ohms at 0 degrees C and rises by about 0.385 ohm per degree near room temperature. The temperature input card passes a small current through it and measures the voltage, so the resistance of the cable becomes part of the reading unless the card can cancel it.

Why it is wired this way

A three-wire input cancels lead resistance by assuming all three leads have the same resistance (same gauge, length and material). Swapping A with a B lead breaks that compensation and gives a wrong reading. Ground the cable shield at the panel end only.

Worked example

Imagine a 50 metre cable with 2 ohms in each conductor. A two-wire connection would add 4 ohms to the reading, about 10 degrees C of error. With a three-wire sensor the card makes two measurements: one through the A lead and a B lead, and one through the two B leads alone. Because the two B leads have the same resistance, the card can subtract the cable out. This only works when the pair of identical leads land on B1 and B2 and the odd lead lands on A. In the lab, power the card first, then land the leads, then bond the shield at the panel end.

Common mistakes

  • Exchanging the single A conductor with one of the B conductors, which breaks the cancellation and gives a drifting reading.
  • Earthing the shield at both ends, which creates a loop that picks up noise.
  • Selecting a channel configured for two-wire or four-wire when the sensor is three-wire.
  • Assuming an open lead reads zero. A broken Pt100 lead normally drives the reading to over-range.

What you can now do

You can terminate a three-wire RTD, explain how the card cancels lead resistance and say which mistakes cause drift or an over-range reading.

Commissioning standard

Measure the sensor with the circuit isolated: roughly 100 ohms at ice-bath temperature and about 107.8 ohms at 20 degrees C, with equal readings from each B lead.

Hints

Hint 1

Power the temperature input card before wiring the sensing element.

Hint 2

Sign up to unlock the full hint sequence.

Hint 3

Sign up to unlock the full hint sequence.

This lesson uses 7 placed components on the lab canvas. Components are vendor-neutral (no proprietary trademarks); the wiring rules apply to any equivalent industrial part.

Sign up to preview

Create a free account to preview this Pro lab; upgrade to open the interactive circuit.

Sign up to preview →

You might also like

Competency and practice field guide

PT100 RTD wiring lesson: practice plan

Direct answer

The learner can identify each conductor, predict healthy resistance or signal behavior, scale temperature and isolate open, short and lead-compensation errors.

Written for instrumentation and PLC learners wiring a platinum RTD through a transmitter or compatible input and interpreting lead-resistance, range and fault evidence.

an isolated instrumentation bench connecting realistic sensors, signal conditioning, PLC channels and measurement evidence while studying PT100 RTD two-, three- and four-wire measurement
System map / 02

NODE 01observable

Scope

PT100 characteristic, element class, temperature range, wire count, lead resistance, excitation, transmitter or RTD input, cable, shield, units and calibration points.

NODE 02observable

Signal path

Temperature through platinum resistance, lead network, measurement circuit, transmitter output or raw value, PLC scaling and independent reference.

NODE 03observable

Baseline practice

At least three known temperature or resistance points matching the declared curve and tolerance.

NODE 04observable

Edge cases

Open element, shorted element, unequal three-wire leads, reversed transmitter polarity, wrong curve, self-heating, noise and restart.

NODE 05observable

Fault practice

An element, lead, connection, excitation, transmitter, input, curve, scaling, installation or calibration mismatch.

NODE 06observable

Transfer to the job

The installed loop checked with current device documentation and traceable resistance or temperature references.

Answer surface / 07

Why does a PT100 use three wires?

A compatible three-wire measurement can compensate for similar lead resistance; the exact terminals and assumptions depend on the input or transmitter circuit.

Can a PT100 connect directly to a PLC?

Only to a compatible RTD input. A standard current or voltage input generally requires an appropriate temperature transmitter.