Wiring 28 — Six-Wire Load Cell and Transmitter

What you'll learn

Terminate a six-wire strain-gauge load cell on a weighing transmitter, including excitation, millivolt signal, sense conductors and shield. Send the transmitter’s conditioned 4–20 mA output to a PLC analog input.

Lab time: ~22 minutes.

Lesson briefing

Six-Wire Load Cell and Transmitter

Terminate a six-wire strain-gauge load cell on a weighing transmitter, including excitation, millivolt signal, sense conductors and shield. Send the transmitter’s conditioned 4–20 mA output to a PLC analog input.

The device in the real world

A load cell is a metal block with strain gauges bonded to it, so a few millivolts appear on its signal wires when weight is applied. Weighing systems for hoppers, silos and platform scales feed these cells with a precise excitation voltage and read the output with a transmitter. Six-wire cells add two sense wires so the transmitter can measure the real excitation voltage at the cell, after the cable losses.

Why it is wired this way

Remote-sense wires let the transmitter compensate excitation voltage drop along the cable. The SIG pair carries only millivolts and is highly noise-sensitive. The shield is bonded at one end and must not carry operating current.

Worked example

Suppose a cell is rated at 2 mV per volt of excitation and the transmitter supplies 10 V. At full load the signal is only 20 mV. If a long cable drops 0.2 V in the excitation leads, the cell actually sees 9.8 V and the signal is 2 percent low, unless the sense wires report that drop back and the transmitter corrects it. The conditioned 4 to 20 mA output then goes to the PLC analog input. Wire the lab by matching the six cell conductors one for one, then powering the transmitter, then the output pair.

Common mistakes

  • Swapping SIG+ and SIG-, so the weight reads backwards.
  • Landing a SENSE wire on an EXC terminal at the transmitter, which removes the cable-loss correction.
  • Earthing the shield at both ends.
  • Routing the signal pair next to motor cables.

What you can now do

You can terminate a six-wire load cell, say what the sense wires are for and send the conditioned output to the PLC.

Commissioning standard

Check the empty-scale output first, then add a known test weight and compare the reading with the expected value.

Hints

Hint 1

Match EXC+, EXC−, SIG+, SIG− and both SENSE conductors one-for-one.

Hint 2

Sign up to unlock the full hint sequence.

Hint 3

Sign up to unlock the full hint sequence.

This lesson uses 6 placed components on the lab canvas. Components are vendor-neutral (no proprietary trademarks); the wiring rules apply to any equivalent industrial part.

Sign up to preview

Create a free account to preview this Pro lab; upgrade to open the interactive circuit.

Sign up to preview →

You might also like

Competency and practice field guide

Load-cell PLC wiring lesson: practice plan

Direct answer

The learner can identify every conductor and reference, verify raw zero and span, scale weight and diagnose polarity, noise, excitation and mechanical errors.

Written for electrical, instrumentation and PLC learners connecting a strain-gauge load cell through excitation and signal conditioning to a usable engineering value.

a technician tracing realistic industrial sensors, signal wiring, PLC inputs and measured trends at an instrumentation learning bench while studying load-cell bridge, transmitter and PLC analog-input wiring
System map / 02

NODE 01observable

Scope

Load range, bridge sensitivity, excitation, signal conductors, shield, junction box, amplifier or transmitter, analog range, PLC resolution, units, calibration points and mechanical installation.

NODE 02observable

Signal path

Applied load through strain bridge, millivolt signal, conditioning, current or voltage loop, PLC raw count, scaling and independent reference weight.

NODE 03observable

Baseline practice

Zero and at least two known loads produce repeatable raw and engineering values within the declared tolerance.

NODE 04observable

Edge cases

Reversed signal, missing excitation, open conductor, overload, creep, vibration, off-center load, ground loop, noise and power return.

NODE 05observable

Fault practice

A mechanical, bridge, excitation, wiring, conditioner, loop, analog-input, scaling or calibration mismatch.

NODE 06observable

Transfer to the job

The complete weighing chain calibrated with traceable loads and current equipment procedures.

Answer surface / 07

Can a load cell connect directly to a PLC analog input?

Many load cells produce a small bridge signal that needs compatible excitation and signal conditioning before a standard PLC voltage or current input can use it.

How do I scale a load cell in a PLC?

Record raw values at known zero and span loads, apply a bounded linear conversion and verify intermediate points and overload behavior.